The CPM 700 monitor serves primarily as a broken bag detector. An alarm is activated when a pre-set particulate emissions level is exceeded.
In addition to the features of the CPM 700 monitor, the CPM 750 monitor adds a 4-20 mA analog output module that allows connection to:
| Transmitter head |
| Material: |
6061 Aluminum |
|
| Protection: |
NEMA-4x |
|
| Power Input: |
± 15 VDC from the CPM 700/750 |
|
| Receiver Head Air Purge Connection: |
1/4 in. (6.35 mm) |
|
| Temperature Range: |
|
| Process: |
10° F - 350° F (-12° C - 177° C) |
|
| Ambient: |
10° F - 135° F (-12° C - 57° C) |
|
| Weight: |
6.6 lbs. (3.0 kg) |
|
| Light Source: |
Light Emitting Diode (LED) |
|
| Receiver head/electronics |
|
| Material: |
Steel |
|
| Protection: |
NEMA Type 4, 12 |
|
| Power Input: |
100-240 VAC, 50/60 Hz |
|
| Air Purge Connection: |
1/4 in. (6.35 mm) |
|
| Temperature Range: |
|
| Process: |
10° F - 350° F (-12° C - 177° C) |
|
| Ambient: |
10° F - 135° F (-12° C - 57° C) |
|
| Hardware Alarm Relays: |
Two |
|
| Relay Type: |
Solid State Relay |
|
| Operating Voltage Range: |
24-280 VAC 25-65 Hz |
|
| Relay Current Rating: |
3A at 45° C ambient |
|
| Relay Off State Leakage: |
2.5 mA RMS at 120 VAC |
|
| Analog Output: |
One; 4-20 mA |
|
| Dimensions: |
8 x 10 x 4 in. (203 x 254 x 102 mm) |
|
| Weight: |
11.8 lb. (5.4 kg) |
|
| Minimum Duct Width: |
3 in. (76.2 mm) |
|
| Maximum Duct Width: |
20 ft. (6 meters) |
|
| Supplied Interconnecting Cable: |
50 ft. (15 meters) |
|